Optimal Blocking Device Placement for Geomagnetic Disturbance Mitigation
- 25 July 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 34 (6) , 2219-2231
Abstract
Geomagnetically induced currents (GICs) introduced by geomagnetic disturbances (GMDs) can damage transformers, increase reactive power losses, and cause reliability issues in power systems. Finding an optimal strategy to place blocking devices (BDs) at transformer neutrals is essential to mitigating the negative impact of GICs. In this paper, we study and solve the problem of optimal BD placement (OBP), aiming at minimizing the damages of GMDs, subject to various practical constraints. In particular, our approach accounts for the potential impact of BD placement to neighboring interconnected systems; we also consider the time-varying nature of the geoelectric field in BD placement. To the best of our knowledge, neither has been considered in the existing works. Under these constraints, the combined complexity of solving the OBP problem on a large-scale system poses a big challenge. To address this, we developed a simulated annealing-based algorithm that can achieve near-optimal solutions for the OBP problem at a reduced computational complexity, while taking the above constraints into account. More importantly, this paper provides a general mathematical framework that can be used to solve various OBP problems, with different objective functions and constraints. We demonstrated the effectiveness and the efficiency of our method by using power systems of various sizes.Keywords
Funding Information
- National Science Foundation (1520864, 1807097)
This publication has 23 references indexed in Scilit:
- Effects of neutral point reactors and series capacitors on geomagnetically induced currents in a high‐voltage electric power transmission systemSpace Weather, 2011
- A polyhedral branch-and-cut approach to global optimizationMathematical Programming, 2005
- Development of a DC Current-Blocking Device for Transformer NeutralsIEEE Transactions on Power Delivery, 2005
- Management of the geomagnetically induced current risks on the national grid company's electric power transmission systemJournal of Atmospheric and Solar-Terrestrial Physics, 2002
- Modelling geomagnetically induced currents produced by realistic and uniform electric fieldsIEEE Transactions on Power Delivery, 1998
- Simulated annealing: a proof of convergenceIEEE Transactions on Pattern Analysis and Machine Intelligence, 1994
- Characteristics of transformer exciting-current during geomagnetic disturbancesIEEE Transactions on Power Delivery, 1991
- Thermodynamical approach to the traveling salesman problem: An efficient simulation algorithmJournal of Optimization Theory and Applications, 1985
- Optimization by Simulated AnnealingScience, 1983
- Monte Carlo sampling methods using Markov chains and their applicationsBiometrika, 1970