Abstract
The contributions in this paper consist of two techniques for power flow analysis and optimization algorithm to optimal integration of distributed generation (DG) sources in radial distribution network (RDN). The 1st technique depends on a mathematical representation to create the bus impedance matrix [Zbus] based on the RDN configuration. The 2nd technique is the Bus-Grouping Optimization Algorithm for any RDN (BGOARDNs) for reducing active and reactive power losses, improving the RDN voltage profile, minimizing the voltage deviation index (VDI) and reducing the annual cost of energy losses through optimal DGs location and sizing. The applicability and effectiveness of the new approach has been verified on the IEEE 33-bus and IEEE 69-bus RDN. It has been observed that the proposed technique method resulted in further improvement in both reducing annual energy losses and saving costs over recent optimization techniques. In the IEEE 33-bus test system, the reduction percentage in active and reactive losses are found to be 65.5% and 65.8% respectively with annual energy cost saving decrement is 65.505%. While in the IEEE 69-bus system, the reduction percentage in active and reactive losses are found to be 69.13% and 65.78% respectively with annual energy cost saving decrement is 69.134%. So, the results of BGOARDNs are better than other techniques.
Funding Information
  • ENET Centre, CEET, VSB-Technical University of Ostrava, 708 00 Ostrava, Czech Republic

This publication has 43 references indexed in Scilit: