An Adaptive Control for UPS to Compensate Unbalance and Harmonic Distortion Using a Combined Capacitor/Load Current Sensing
Authors:
- G. EscobarGEG. Escobar
- P. MattavelliPMP. Mattavelli
- A. M. StankovicASA. M. Stankovic
- Andrs A. ValdezAndrs A. Valdez
- Jesus Leyva-RamosJLJesus Leyva-Ramos
- 12 March 2007
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 54 (2) , 839-847
Abstract
This paper investigates the control of an uninterruptible power supply (UPS) using a combined measurement of capacitor and load currents in the same current sensor arrangement. The purpose of this combined measurement is, on one hand, to reach a similar performance as that obtained in the inductor current controller with load current feedforward and, on the other hand, to easily obtain an estimate of the inductor current for overcurrent protection capability. Based on this combined current measurement, a voltage controller based on resonant harmonic filters is investigated in order to compensate for unbalance and harmonic distortion on the load. Adaptation is included to cope with uncertainties in the system parameters. It is shown that after transformations the proposed controller gets a simple and practical form that includes a bank of resonant filters, which is in agreement with the internal model principle and corresponds to similar approaches proposed recently. The controller is based on a frequency-domain description of the periodic disturbances, which include both symmetric components, namely, the negative and positive sequence. Experimental results on the output stage of a three-phase three-wire UPS are presented to assess the performance of the proposed algorithmKeywords
This publication has 12 references indexed in Scilit:
- Application of a Sinusoidal Internal Model to Current Control of Three-Phase Utility-Interface ConvertersIEEE Transactions on Industrial Electronics, 2005
- Dissipativity-based adaptive and robust control of UPS in unbalanced operationIEEE Transactions on Power Electronics, 2003
- Stationary frame current regulation of PWM inverters with zero steady-state errorIEEE Transactions on Power Electronics, 2003
- PWM voltage and current control of four-leg VSI2002
- Synchronous-frame harmonic control for high-performance AC power suppliesIEEE Transactions on Industry Applications, 2001
- Dissipativity-based adaptive and robust control of UPSIEEE Transactions on Industrial Electronics, 2001
- Control topology options for single-phase UPS invertersIEEE Transactions on Industry Applications, 1997
- DSP control of high-power UPS systems feeding nonlinear loadsIEEE Transactions on Industrial Electronics, 1996
- A two-switch high-performance current regulated DC/AC converter moduleIEEE Transactions on Industry Applications, 1995
- Waveform compensation of PWM inverter with cyclic fluctuating loadsIEEE Transactions on Industry Applications, 1988