Comparative Study of Transformer-Type Superconducting Fault Current Limiters Considering Magnetic Saturation of Iron Core
Authors:
- H. YamaguchiHYH. Yamaguchi
- 25 September 2006
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Magnetics
- Vol. 42 (10) , 3386-3388
Abstract
A transformer-type superconducting fault current limiter (SCFCL) is one of the fault current limiters which have been proposed to reduce the fault currents in power transmission lines. For this type of fault current limiter, a circuit configuration with a shunt inductor is possible to divert the fault current. In this paper, the transient performances of the transformer-type SCFCLs with and without the shunt inductor when a short-circuit fault occurs, are analyzed by simulation and compared considering the magnetic saturation of the transformer iron core, thereby clarifying the influence of magnetic saturation on the current limiting characteristics of these SCFCLs. Experimental results are included to justify the simulation analysesKeywords
This publication has 3 references indexed in Scilit:
- Effect of Magnetic Saturation on the Current Limiting Characteristics of Transformer Type Superconducting Fault Current LimiterIEEE Transactions on Applied Superconductivity, 2006
- Design and Testing of 230 V Inductive Type of Superconducting Fault Current Limiter With an Open CoreIEEE Transactions on Applied Superconductivity, 2005
- Characteristics Analysis of Transformer Type Superconducting Fault Current LimiterIEEE Transactions on Applied Superconductivity, 2004