Hazardous-Rated Electrical Equipment and the Arc-Flash Hazard
Authors:
- Rick MendlerRMRick Mendler
- Rehanul HasanRHRehanul Hasan
- Jean-Baptiste TrolleJTJean-Baptiste Trolle
- Nabil L. MinaNMNabil L. Mina
- 21 April 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 51 (5) , 4335-4341
Abstract
This paper evaluates the relationship between hazardous-rated electrical equipment, which is suitable for installation in Class I, Division 1 (Zone 1), or Division 2 (Zone 2) locations, and an arc-rated switchgear, which is designed to withstand the effects of an internal arcing fault. Using UL 1203 (Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations), IEEE C37.20.7 (IEEE Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults), and the paper titled “Pressure Developed by Arcs,” this paper will explore the applicability of hazardous-rated equipment in the protection of personnel from an arc-flash hazard.Keywords