Voltage sag influence on controlled three‐phase grid‐connected inverters according to the Spanish grid code
Open Access
- 27 March 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 14 (10) , 1882-1892
Abstract
To ensure the safe operation of the grid, there are some requirements to be taken into consideration to connect power converters. During abnormal conditions – e.g. during voltage sags –, the control of the converters is a very important key to guarantee power quality and good behaviour of the distributed generation system. The aim of this study is to employ two possible control strategies for a grid‐connected inverter according to the Spanish grid code, and to analyse the behaviour of the output voltages during both symmetrical and unsymmetrical voltage sags. The analytical development shows the sag influence on currents, voltages, active and reactive powers. These influences are explained through Ku transformation in the synchronous reference frame, thus giving a representation for electrical variables easiest to analyse. The results show how control strategies affect the converter behaviour and how they can support the main grid during faults through the control of active and reactive power injection. Sags with different durations and depths have been taken into account, which can provoke critical values for electrical magnitudes and can lead to the violation of the grid code. The proposed control strategies study has been validated by means of both simulations in M atlab TM –Simulink and experimental results.Keywords
This publication has 31 references indexed in Scilit:
- A Current Limiting Strategy to Improve Fault Ride-Through of Inverter Interfaced Autonomous MicrogridsIEEE Transactions on Smart Grid, 2016
- Control Strategy to Maximize the Power Capability of PV Three-Phase Inverters During Voltage SagsIEEE Transactions on Power Electronics, 2015
- Control strategy of low voltage ride-through for grid-connected photovoltaic inverter2015
- Power Control of Grid-Connected Converters Under Unbalanced Voltage ConditionsIEEE Transactions on Industrial Electronics, 2014
- Helping all generations of photo‐voltaic inverters ride‐through voltage sagsIET Power Electronics, 2014
- Active and Reactive Power Strategies With Peak Current Limitation for Distributed Generation Inverters During Unbalanced Grid FaultsIEEE Transactions on Industrial Electronics, 2014
- High-Power VSC-Based Simultaneous Positive- and Negative-Sequence Voltage RegulatorIEEE Transactions on Power Delivery, 2014
- Positive- and negative-sequence control of grid-connected photovoltaic systems under unbalanced voltage conditions2013
- Integrated Control Technique for Compliance of Solar Photovoltaic Installation Grid CodesIEEE Transactions on Energy Conversion, 2012