Abstract
In accordance with the USCG type approval procedure, a fixed CO₂ fire-extinguishing system is mounted on a ship after obtaining type approval. For it to pass the vibration test for type approval, an appropriate vibration resistance design is required. In this study, we analyzed the severity of the vibration test standard UL2127 and developed a modularized test method for USCG type approval. Based on the proposed test method, the vibration response characteristics of each module were evaluated with three-axis vibration test machines. In the case of the cylinder module, damage was caused by excessive vibrations due to resonance, which can be mitigated by changing the rigidity of the boundary structure and shifting the natural frequency out of the frequency range of interest.
Funding Information
  • Ministry of Oceans and Fisheries
  • Korea Institute of Marine Science and Technology promotion

This publication has 4 references indexed in Scilit: