The article presents the results of comparative investigations of partial discharges in two insulation systems; aramid-enhanced cellulose paper-mineral oil, and pure cellulose paper-mineral oil. Partial discharges were investigated in a diagonal electric field with vertical and horizontal components. This field is treated as the most dangerous for insulation. The research was carried out on Nomex® 910 paper and cellulose paper samples, each paper being 0.25 mm thick. Samples of the two materials were tested at four levels of moisture. The inception voltage of partial discharges of all samples tested decreased as their moisture content increases. It was also proved that Nomex® 910 has a significantly higher partial discharge inception voltage than the cellulose paper, although this difference decreased with increasing moisture content.Keywords
Funding Information
- Ministerstwo Edukacji i Nauki (04/41/SBAD/4413)
This publication has 2 references indexed in Scilit:
- Moisture Migration in an Oil-Paper Insulation System in Relation to Online Partial Discharge Monitoring of Power TransformersEnergies, 2016
- Water saturation limit of insulating liquids and hygroscopicity of cellulose in aspect of moisture determination in oil-paper insulationIEEE Transactions on Dielectrics and Electrical Insulation, 2016