Design of the Optimal ULTC Parameters in Distribution System With Distributed Generations
Authors:
- Miyoung KimMKMiyoung Kim
- Ryoichi HaraRHRyoichi Hara
- Hiroyuki KitaHKHiroyuki Kita
- 16 December 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 24 (1) , 297-305
Abstract
In order that the supply of electric power remain stable and sustainable, a certain level of power quality must be maintained while securing energy resources and resolving environmental issues. The distributed generation (DG) has become an essential and indispensable element of such distribution systems from both an environmental and an energy security perspective. However, the installation of DGs in distribution systems may cause variations of voltage on distribution feeder because the DG power outputs may change randomly and dramatically. Generally, the sending voltage at substation in distribution systems can be regulated by an under load tap changer (ULTC) designed to maintain customers' receiving voltages within a predetermined range. Voltage regulation performed by ULTC calls for two parameters: the equivalent impedance and the load center voltage. Therefore, in distribution networks with DG interconnections, these parameters should be designed with attention not only to load variations but also to DG outputs. This paper proposes a method for designing ULTC parameters with reference to variations in DG output. The proposed algorithm is tested with IEEE 13-node system and Korean model network. The results demonstrate the validity of the proposed design method for varying DG distribution.Keywords
This publication has 17 references indexed in Scilit:
- Radial MV networks voltage regulation with distribution management system coordinated controllerElectric Power Systems Research, 2008
- Voltage control with on-load tap changers in medium voltage feeders in presence of distributed generationElectric Power Systems Research, 2007
- Computation of Locational and Hourly Maximum Output of a Distributed Generator Connected to a Distribution FeederIEEJ Transactions on Power and Energy, 2006
- Influence of distribution voltage control methods on maximum capacity of distributed generatorsElectrical Engineering in Japan, 2004
- Integration of dispersed generation on distribution networks-impact studies2003
- A study on the optimal voltage regulation methods in power distribution systems interconnected with dispersed energy storage and generation systems2002
- Main transformer ULTC and capacitors scheduling by simulated annealing approachInternational Journal of Electrical Power & Energy Systems, 2001
- Advanced voltage regulation method at the power distribution systems interconnected with dispersed storage and generation systemsIEEE Transactions on Power Delivery, 2000
- Adaptive neuro-fuzzy inference system for volt/var control in distribution systemsElectric Power Systems Research, 1999