Investigations of cable termination thermal analysis under continuous current loading
Open Access
- 9 July 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 14 (19) , 4122-4131
Abstract
In this study, alternative methodological approaches are used to calculate the temperature distribution along the length of the termination of a single core cable. The analysis is done based on the heat flow produced by cable conductor and heat transfer by conduction, convection, and radiation. A comparison of the obtained temperature distribution along the cable termination length and the cable adjacent part using an analytical method with the results of both actual measurements and calculations done by finite‐element method (FEM) was done, which revealed a good agreement for various load currents. The performed computations by using the analytical method and FEM gave results within ±6% difference with measured conductor temperature. The influences of the cable loading current and the insulation thermal conductivity of the cable termination on its maximum temperature rise along the length of the cable termination have been discussed. Finally, this study is concerned with the measurement and prediction of the temperature distribution in the cable termination. More clarifications of the used measured technique and prediction approaches are presented in the study.Keywords
This publication has 18 references indexed in Scilit:
- Electrothermal Analysis of Low- and Medium-voltage Cable JointsElectric Power Components and Systems, 2015
- Thermal modeling of medium voltage cable terminations under square pulsesIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Theoretical research on temperature field of power cable joint with FEM2012
- A new approach to underground cable performance assessmentElectric Power Systems Research, 2008
- Stress grading materials for cable terminations under fast-rise time pulsesIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Theoretical model to calculate steady-state and transient ampacity and temperature in buried cablesIEEE Transactions on Power Delivery, 2003
- Calculation of the Sensitivity of Power Cable Ampacity to Variations of Design and Environmental ParametersIEEE Transactions on Power Apparatus and Systems, 1984
- Cable Terminations for Force-Cooled High-Voltage Pipe-Type Cable SystemsIEEE Transactions on Power Apparatus and Systems, 1982
- A Numerical Procedure for the Calculation of the Temperature Rise and Ampacity of Underground CablesIEEE Transactions on Power Apparatus and Systems, 1981
- Thermal Analysis of Cable Sealing EndsIEEE Transactions on Power Apparatus and Systems, 1980