Application of FRA polar plot technique to diagnose internal faults in power transformers
Authors:
- 1 July 2014
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. pp (19325517) , 1-5
Abstract
Frequency response analysis (FRA) technique has become a popular and reliable diagnostic tool in detecting various winding deformation in power transformers. Although the popularity of FRA is growing rapidly, interpretation of FRA signature requires high expertise. While all frequency response analyzers currently used for FRA signature measurement are capable in plotting both magnitude and angle of either the transfer function or impedance of each transformer winding, only magnitude is used for fault identification and quantification. This paper presents a new technique for FRA signature interpretation. The proposed technique relies on incorporating both magnitude and angle of the FRA signature in one polar plot. Results show that, polar plot is more capable in identifying and quantifying faults within power transformer than using only the magnitude of FRA signature. The proposed technique is easy to implement in any frequency response analyzer.Keywords
This publication has 15 references indexed in Scilit:
- Understanding power transformer frequency response analysis signaturesIEEE Electrical Insulation Magazine, 2013
- Internal failure analysis of transformer windings2012
- A novel algorithm to detect internal transformer faults2011
- Experimental and theoretical investigation of disc space variation in real high-voltage windings using transfer function methodIET Electric Power Applications, 2010
- Interpretation of Transformer FRA Responses— Part II: Influence of Transformer StructureIEEE Transactions on Power Delivery, 2010
- Life Extension of a Group of Western Power Transformers2010
- Effect of Core Magnetization on Frequency Response Analysis (FRA) of Power TransformersIEEE Transactions on Power Delivery, 2008
- Thermal monitoring on power transformers2008
- Transfer Function Method to Diagnose Axial Displacement and Radial Deformation of Transformer WindingIEEE Power Engineering Review, 2002
- Mechanical stresses in transformer windingsJournal of the Institution of Electrical Engineers - Part II: Power Engineering, 1946