Biofouling control with ozone at the Bergen Generating Station

Authors:
  • RSR. Sugam
    R. Sugam
  • CGC. R. Guerra
    C. R. Guerra
  • JDJ. L. DelMonaco
    J. L. DelMonaco
  • JSJ. H. Singletary
    J. H. Singletary
  • WSW. A. Sandvik
    W. A. Sandvik

Abstract
The results of a study designed to evaluate the effectiveness of ozone as an alternative to chlorine for condenser biofouling control in a once-through cooling system are reported. Tests were conducted at PSE and G's Bergen Generating Station using a pilot-scale condenser system to simulate plant condenser operations. Three model condensers were operated under identical conditions with only the biocide treatment differing. Comparisons of ozone and chlorine were made and the minimum effective levels of each were determined by daily measurements of the heat transfer coefficient across the model condenser tubes and/or the water side pressure drop. Final evaluation was based on the mass of biofouling material collected from the tubewalls. Test results indicate that chlorine is capable of effective biofouling control when applied for 2 hours/day at a level as low as 0.1 mg/l. Ozone, applied on the same schedule, requires 0.5 mg/l for effective control. The results of this study are representative of only the Bergen site. Water quality at each particular site will influence the development of the biofouling organisms, the chemical reactions of the biocides, and therefore, the effectiveness of the treatment methodology. The results suggest that further examination of ozonation for biofouling control is warranted.more » Although much more costly than chlorine, its effects on indigenous ecosystems may prove ozone to be better suited for application at selected power plants. It must be emphasized, however, that much more information is necessary before ozone can be recommended as an environmentally acceptable alternative to chlorine.« less