Optimized Design of Full-Bridge Modular Multilevel Converter With Low Energy Storage Requirements for HVdc Transmission System
Authors:
- Cong ZhaoCZCong Zhao
- Yaohua LiYLYaohua Li
- Zixin LiZLZixin Li
- Ping WangPWPing Wang
- Xun MaXMXun Ma
- Yongjie LuoYLYongjie Luo
- 27 January 2017
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 33 (1) , 97-109
Abstract
Modular multilevel converter (MMC) is a well proved circuit topology in voltage source converter based high voltage direct current (VSC-HVDC) transmission systems. As is known, the conventional half bridge submodule (HBSM) based MMC-HVDC is not suitable for overhead line transmission applications. In addition, high energy storage requirements, i.e. large capacitance is inevitable. The conventional design of the full-bridge submodule (FBSM) based MMC (F-MMC) usually does not utilize the negative voltage state of FBSM in normal operation. Considering the same dc voltage as with the HBSM case and utilizing the negative voltage state of the FBSM, this paper presents the design method of the power transmission capability of a single FBSM. Meanwhile, an optimized energy storage capacitance design method of the FBSM is proposed. With this method, the capacitance of FBSM can be reduced significantly. The correctness and effectiveness of the proposed method is verified by the simulation of a ±160 kV VSC-HVDC MMC and the comparison results of the dc short fault blocking and ride through capability are also provided.Keywords
This publication has 29 references indexed in Scilit:
- Power Module Capacitor Voltage Balancing Method for a ±350-kV/1000-MW Modular Multilevel ConverterIEEE Transactions on Power Electronics, 2015
- Closed-Loop Discontinuous Modulation Technique for Capacitor Voltage Ripples and Switching Losses Reduction in Modular Multilevel ConvertersIEEE Transactions on Power Electronics, 2014
- Impacts of Three MMC-HVDC Configurations on AC System Stability Under DC Line FaultsIEEE Transactions on Power Systems, 2014
- Protection of Nonpermanent Faults on DC Overhead Lines in MMC-Based HVDC SystemsIEEE Transactions on Power Delivery, 2012
- Capacitor voltage ripple shaping in modular multilevel converters allowing for operating region extension2011
- VSC-HVDC system protection: A review of current methods2011
- Efficient Modeling of Modular Multilevel HVDC Converters (MMC) on Electromagnetic Transient Simulation ProgramsIEEE Transactions on Power Delivery, 2010
- LCC Analysis of Different Resonant Circuits and Solid-State Circuit Breakers for Medium-Voltage GridsIEEE Transactions on Power Delivery, 2006
- A DC Hybrid Circuit Breaker With Ultra-Fast Contact Opening and Integrated Gate-Commutated Thyristors (IGCTs)IEEE Transactions on Power Delivery, 2006
- Circuit breaker concepts for future high-power DC-applications2005