A Setting-Free Differential Protection for Power Transformers Based on Second Central Moment
Authors:
- 1 January 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 34 (2) , 750-759
Abstract
This paper describes a differential algorithm for the protection of a three-phase transformer to differentiate transient phenomena, such as inrush currents and external faults from solid and turn-to-turn faults. This algorithm is based on the behavior of the second central moment (SCM) to identify the kind of event. Instantaneous differential currents are used as input signals to the algorithm once they are filtered and normalized. The algorithm compares the magnitude of the SCM with an established threshold based on the binomial distribution to achieve a successful identification of the event. If the magnitude of the SCM is above the limit, the algorithm identifies the event as a fault condition. Otherwise, the event is determined as a transient event or a steady-state condition. The threshold is setting-free if the transformer parameters are changed or if the harmonic content of the differential current varies. Also, the threshold does not have to be recalculated if the power system is modified. The D index was introduced to improve the fault-detection time when the current transformers experience saturation. This index uses the magnitude of the SCM as a basis and is compared with an established limit to detect the fault current. Both indices run in parallel, and if any of them does cross its respective threshold, a fault condition is determined. The algorithm is tested in a real-time digital simulator and is implemented in MATLAB. The algorithm was compared against the conventional differential protection with harmonic restraint to evaluate the performance of both indices in critical conditions. The results validate the performance of the algorithm and indicate that it can be the basis of a new algorithm to protect power transformers.Keywords
Funding Information
- Consejo Nacional de Ciencia y Tecnología (257068, CB-2015-01)
This publication has 35 references indexed in Scilit:
- Using mathematical morphology to discriminate between internal fault and inrush current of transformersIET Generation, Transmission & Distribution, 2016
- Power Transformer Differential Protection Using the Boundary Discrete Wavelet TransformIEEE Transactions on Power Delivery, 2015
- Speed of line protection - can we break free of phasor limitations?2015
- The Impact of Current-Transformer Saturation on Transformer Differential ProtectionIEEE Transactions on Power Delivery, 2014
- Hyperbolic S -transform-based method for classification of external faults, incipient faults, inrush currents and internal faults in power transformersIET Generation, Transmission & Distribution, 2012
- Extended Park's vector approach-based differential protection of three-phase power transformersIET Electric Power Applications, 2012
- Power Transformer Characteristics and Their Effects on Protective Relays2007
- A current-based solution for transformer differential protection. I. Problem statementIEEE Transactions on Power Delivery, 2001
- A Better Bound on the VarianceThe American Mathematical Monthly, 2000
- Note on a Method for Calculating Corrected Sums of Squares and ProductsTechnometrics, 1962