Theoretical study of simultaneous water and VOCs adsorption and desorption in a silica gel rotor
- 17 December 2007
- journal article
- Published by Hindawi Limited in Indoor Air
- Vol. 18 (1) , 37-43
Abstract
One-dimensional partial differential equations were used to model the simultaneous water and VOC (Volatile Organic Compound) adsorption and desorption in a silica gel rotor which was recommended for indoor air cleaning. The interaction among VOCs and moisture in the adsorption and desorption process was neglected in the model as the concentrations of VOC pollutants in typical indoor environment were much lower than that of moisture and the adsorbed VOCs occupied only a minor portion of adsorption capacity of the rotor. Consequently VOC transfer was coupled with heat and moisture transfer only by the temperatures of the rotor and the air stream. The VOC transfer equations were solved by discretizing them into explicit up-wind finite differential equations. The model was validated with experimental data. The calculated results suggested that the regeneration time designed for dehumidification may be prolonged to allow complete removal of the VOC pollutants from the rotor. The regeneration temperature designed for dehumidification provides considerable efficiency for indoor air cleaning. The application of the model in estimating the cleaning capacity of the rotor for VOC pollutants was demonstrated. Silica gel rotors, usually used to dehumidify air, were found to be effective to remove VOCs by experiments recently. But the removal characteristics of VOCs are different from that of moisture. Therefore, the rotor structure and operating parameters for dehumidification needs to be optimized for the use of removing moisture and VOCs. This paper gives a way for the optimization.Keywords
This publication has 14 references indexed in Scilit:
- Modeling and simulation of desiccant wheel for air conditioningEnergy and Buildings, 2006
- Desiccant HVAC systems for commercial buildingsApplied Thermal Engineering, 2002
- Effects of wall thickness on the heat and moisture transfers in desiccant wheels for air dehumidification and enthalpy recoveryInternational Communications in Heat and Mass Transfer, 2002
- Studies on solid desiccant based hybrid air-conditioning systemsApplied Thermal Engineering, 2001
- Dehumidification and Simultaneous Removal of Selected Pollutants from Indoor Air by a Desiccant Wheel Using a 1M Type DesiccantJournal of Solar Energy Engineering, 1999
- Heat and mass transfer in composite desiccant pore structures for dehumidificationSolar Energy, 1998
- Moisture transport in silica gel packed beds—I.Theoretical studyInternational Journal of Heat and Mass Transfer, 1987
- Open-Cycle Desiccant Air Conditioning as an Alternative to Vapor Compression Cooling in Residential ApplicationsJournal of Solar Energy Engineering, 1984
- Coupled heat and mass transfer in regenerators—prediction using an analogy with heat transferInternational Journal of Heat and Mass Transfer, 1972
- THE ADSORPTION OF GASES ON PLANE SURFACES OF GLASS, MICA AND PLATINUM.Journal of the American Chemical Society, 1918