Analysis of 0.1-Hz Var Oscillations in Solar Photovoltaic Power Plants
- 7 November 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Sustainable Energy
- Vol. 14 (1) , 734-737
Abstract
Oscillations with very low frequency at 0.1 Hz, have been observed in voltage and var in practical solar photovoltaic (PV) systems when power exporting ramps up to a certain level. This letter provides an explanation on the formation of 0.1-Hz oscillations and identifies three critical factors that lead to the oscillations: communication delay between the plant-level control and the inverter-level control, high volt/var sensitivity at a high power exporting level, and the volt-var feedback system consisting of the plant control, inverter control and the grid impact. Furthermore, a critical feature of the 0.1-Hz oscillation is also explained: why oscillations appear only in voltage and var, but not in real power.Keywords
Funding Information
- US Department of Energy Solar Energy Technology Office (DE-EE-0008771)
- Electric Power Research Institute (10014844)
This publication has 5 references indexed in Scilit:
- Differentiating between plant level and inverter level voltage control to bring about operation of 100% inverter based resource gridsElectric Power Systems Research, 2022
- Real-World Subsynchronous Oscillation Events in Power Grids With High Penetrations of Inverter-Based ResourcesIEEE Transactions on Power Systems, 2022
- Stability Control for Wind in Weak GridsIEEE Transactions on Sustainable Energy, 2018
- Modeling Type-4 Wind in Weak GridsIEEE Transactions on Sustainable Energy, 2018
- An Explanation of Oscillations Due to Wind Power Plants Weak Grid InterconnectionIEEE Transactions on Sustainable Energy, 2017