Efficient Unbalanced Three-Phase Network Modelling for Optimal PV Inverter Control
Open Access
Abstract
High penetration levels of renewable energy generation in the distribution network require voltage regulation to avoid excessive voltage at generating nodes. To effectively control the network and optimize network hosting capacity, the distribution system operator must have an efficient model for power flow analysis. This paper presents the formulas and steps to express the power flow analysis equations of an unbalanced 3-phase network in matrix form suited to programmed solutions. A benchmark MATLAB/Simulink network with unbalanced distribution lines, photovoltaic inverters, and loads is built to verify the matrix model. To demonstrate the application of the model, the control of reverse energy flow from the photovoltaic inverters to keep the voltage in the network below the regulated level is simulated. Two decentralized control algorithms are applied in the network, including an on/off and a multi-objective constrained optimization controller. The detailed construction of the optimization problem for the 3-phase network in matrix form, which is consistent with the power flow calculation, is described. Simulation with the control methods over a day shows that the total active power of the on/off and optimized controllers deliver 41.92% and 99.39% of the available solar power, respectively, while maintaining the network node voltages within limits.Keywords
Funding Information
- ECCO Energy Community Co-operative (1800CHF)
This publication has 27 references indexed in Scilit:
- Developed generalised unified power flow controller model in the Newton–Raphson power‐flow analysis using combined mismatches methodIET Generation, Transmission & Distribution, 2016
- Non-linear analytic approaches of power flow analysis and voltage profile improvement2015
- A Linear Three-Phase Load Flow for Power Distribution SystemsIEEE Transactions on Power Systems, 2015
- Multi-objective coordinated droop-based voltage regulation in distribution grids with PV systemsRenewable Energy, 2014
- Improved voltage regulation strategies by PV inverters in LV rural networks2012
- Use of an Interline Power Flow Controller Model for Power Flow AnalysisEnergy Procedia, 2012
- The load flow calculation in unbalanced radial electric networks with distributed generation2007
- Statcom and load tap changing transformer (LTC) in Newton Raphson Power Flow: Bus voltage constraint and losses2007
- Continuation Three-Phase Power Flow: A Tool for Voltage Stability Analysis of Unbalanced Three-Phase Power SystemsIEEE Transactions on Power Systems, 2005
- Newton-Raphson method in complex form [power system load flow analysis]IEEE Transactions on Power Systems, 1997