Abstract
This paper presents a theory for the creation of harmonics by resonance in converter-grid systems. A harmonic of this type is usually not present or observable under normal operation, but may suddenly appear, with a growing magnitude and at a frequency that coincides with a system resonance frequency. The growth may be unbounded, leading eventually to shutdown of the converter or other components in the system due to protection or physical damage, but often it stops after certain time and the harmonics sustain themselves at a constant magnitude. The latter is the focus of this work and is identified as a result of system operation changing from an initially unstable mode to a critically stable mode, achieved via a self-adjusting process. Small-signal sequence impedance models are used to explain this self-adjusting process and to determine the resulting harmonic responses. Experimental measurements are presented to validate the theory and to demonstrate the characteristics of this type of harmonics.Keywords
Funding Information
- Science and Technology Project
- State Grid Corporation of China
This publication has 18 references indexed in Scilit:
- Sequence Impedance Modeling of Modular Multilevel ConvertersIEEE Journal of Emerging and Selected Topics in Power Electronics, 2017
- A Refined Frequency Scan Approach to Sub-Synchronous Control Interaction (SSCI) Study of Wind FarmsIEEE Transactions on Power Systems, 2015
- Aggregation and Amplification of Wind-Turbine Harmonic Emission in a Wind ParkIEEE Transactions on Power Delivery, 2015
- Mitigation of Inverter-Grid Harmonic Resonance by Narrow-Band DampingIEEE Journal of Emerging and Selected Topics in Power Electronics, 2014
- On the Zero-Crossing Distortion in Single-Phase PFC ConvertersIEEE Transactions on Power Electronics, 2004
- A frequency scanning method for the identification of harmonic instabilities in HVDC systemsIEEE Transactions on Power Delivery, 1995
- Reader's guide to subsynchronous resonanceIEEE Transactions on Power Systems, 1992
- Power system harmonic resonance-a documented caseIEEE Transactions on Industry Applications, 1990
- Theoretical analysis of harmonic instability in a.c.-d.c. convertorsProceedings of the Institution of Electrical Engineers, 1970
- Harmonic instability between controlled static convertors and a.c. networksProceedings of the Institution of Electrical Engineers, 1967