Calibration of PMUs with a reference grade calibrator
Authors:
- 1 August 2014
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 05891485,p. 678-679
Abstract
The calibration of PMUs according to the standard IEEE C37.118.1 requires an important amount of data processing before the error on values such as TVE (Total Vector Error), FE (Frequency Error) or ROCOF (Rate Of Change Of Frequency) can be established. The aim of this paper is to present how this processing is implemented in the PMU reference grade calibrator developed at METAS. Calibration results made on a commercial PMU are also presented.Keywords
This publication has 1 reference indexed in Scilit: