Abstract
At present time complex generating unit models with a great number of parameters are implemented for the emergency control in power systems. Identification of these parameters is a challenging problem. State-of-the-industry measurement devices allow calculating electrical parameters during electromechanical disturbances. That is why one can use simplified generating unit models, parameters of which can be calculated using field measurements. In particular, generating units damping properties might be estimated. The proposed method involves the synchronous machine damping power estimation by means of the measurements approximation during dynamic disturbances. This value allows determining the generating unit capability to damp power system oscillations. The method was examined in MATLAB Simulink and by means of JSC “STC UPS” physical electrodynamic simulator. One can apply obtained results in the power system emergency control and in a wide variety of problems related to dynamic transients calculation and analysis.Keywords
This publication has 6 references indexed in Scilit:
- Defining the equivalent inertia constant of generating unit based on electromechanical transient measurements2016
- Estimation of the Instantaneous Values of the Electrical Operating Parameters in the Ac Network1Power Technology and Engineering, 2016
- Estimating the instantaneous values of the state parameters during electromechanical transients2015
- Numerical Investigation on the Damping Property in Power System Transient BehaviorIEEE Transactions on Power Systems, 2013
- Modeling of Damping for Power System Stability AnalysisElectric Power Components and Systems, 2004
- Analysis of Damping and Synchronizing Torques Part I-A General Calculation MethodIEEE Transactions on Power Apparatus and Systems, 1979