Permanent Emergency LED Lamp Based on a Series Single-Switch Resonant Converter With Battery Clamp
- 3 November 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 69 (10) , 9992-10000
Abstract
Permanent emergency lighting is a safety device whose lamp is always on and continues to operate when a mains failure occurs. The circuit has to charge the battery and drive the lamp while the grid is present and keep the lamp running from the battery in case of mains failure. This might require up to three different converters: front-end converter, electronic ballast, and battery charger. Since an emergency lamp must be on for as long as the local regulations require during a grid failure, efficiency is key. This article presents a permanent emergency lamp based on a series resonant current regulator that operates both as a ballast and as a battery charger. In this circuit, the power converter is placed in series with the LED array, operating as a controllable nondissipative impedance. A methodology based on the study of energy balances during resonant operation intervals is presented, aiming to design and build a laboratory prototype with low component count and high efficiency.Keywords
Funding Information
- Ministry of Science, and Innovation of the Government of Spain (PID2019-105568RB-I00)
This publication has 21 references indexed in Scilit:
- A 2.4-GHz CMOS Class-E Synchronous RectifierIEEE Transactions on Microwave Theory and Techniques, 2016
- An Analytical Approach for the Design of Class-E Resonant DC–DC ConvertersIEEE Transactions on Power Electronics, 2016
- Matching LED and Driver Life Spans: A Review of Different TechniquesIEEE Industrial Electronics Magazine, 2015
- Performance Limits, Design and Implementation of mm-Wave SiGe HBT Class-E and Stacked Class-E Power AmplifiersIEEE Journal of Solid-State Circuits, 2014
- Sinusoidal-Ripple-Current Charging Strategy and Optimal Charging Frequency Study for Li-Ion BatteriesIEEE Transactions on Industrial Electronics, 2012
- A Three-in-One Converter for Regular and Emergency Lighting ApplicationsIEEE Transactions on Industry Applications, 2009
- Evaluation of a Low-Cost Permanent Emergency Lighting System Based on High-Efficiency LEDsIEEE Transactions on Industry Applications, 2005
- A high efficient low output voltage (3.3 V) single stage AC/DC power factor correction converter2002
- A microcontroller-based emergency ballast for fluorescent lampsIEEE Transactions on Industrial Electronics, 1997
- Maximum frequency and optimum performance of class E power amplifiersIEE Proceedings - Circuits, Devices and Systems, 1994