Turn-to-Turn Fault Diagnosis on Three-Phase Power Transformer Using Hybrid Detection Algorithm
Open Access
- 15 March 2021
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 11 (6) , 2608
Abstract
A power transformer (PT) in power generation or transmission is critical to maintaining electrical continuity. Fault detection on a PT is needed, especially of incipient faults, which are often caused by a turn-to-turn fault (TTF) before it develops into a more severe fault. We use a hybrid algorithm between conventional and modern techniques to detect a developing fault in a PT. The current response signals from a negative sequence current directional algorithm, extended park vector algorithm (EPVA), differential negative sequence current, and EPVA-fuzzy system are combined to distinguish the possibility of a TTF. The subalgorithms are combined using a hybrid detection algorithm to distinguish the faults. The model is a 10 MVA, three-phase PT with Δ-Y configuration 150/300 kV, simulated using MATLAB Simulink software. The results show that by combining the subalgorithms, several limitations are distinguished within the TTF with a slight increase in accuracy.Keywords
This publication has 20 references indexed in Scilit:
- Power Transformer Fault Diagnosis Based on Dissolved Gas Analysis by Correlation Coefficient-DBSCANApplied Sciences, 2020
- Parameter Estimation of Electric Power Transformers Using Coyote Optimization Algorithm With Experimental VerificationIEEE Access, 2020
- New protection scheme for power transformer based on superimposed differential currentIET Generation, Transmission & Distribution, 2018
- Multi-objective artificial bee colony algorithm to estimate transformer equivalent circuit parametersPeriodicals of Engineering and Natural Sciences (PEN), 2017
- Efficient method for discrimination between inrush current and internal faults in power transformers based on the non‐saturation zoneIET Generation, Transmission & Distribution, 2017
- Comparing Power Transformer Turn-to-Turn Faults Protection Methods: Negative Sequence Component Versus Space-Vector AlgorithmsIEEE Transactions on Industry Applications, 2016
- Fault discrimination scheme for power transformer using random forest techniqueIET Generation, Transmission & Distribution, 2016
- Turn‐to‐earth fault modelling of power transformer based on symmetrical componentsIET Generation, Transmission & Distribution, 2013
- Power Transformer Differential Protection Based on Clarke's Transform and Fuzzy SystemsIEEE Transactions on Power Delivery, 2011
- Fuzzy logic-based relaying for large power transformer protectionIEEE Transactions on Power Delivery, 2003