As a reliable and non-destructive technique, frequency response analysis (FRA) has been widely recognized for transformer winding deformation detection and assessment. In this paper, frequency response functions (FRFs) are obtained by two different FRA measurement connection ways, namely end to end voltage ratio and transfer voltage ratio measurements. At the same time, according to the two ways, sensitivities of the FRFs to electrical parameters of the equivalent circuit model of the transformer winding are investigated. Based on Tellegen theorem, adjoint network method is derived to calculate the values of the sensitivities of FRFs to electrical parameters. Meanwhile, the sensitivity characteristics of circuit parameters are studied. In addition, by comparing the sensitivity results of the two ways, the variation laws of the sensitivities under the two different connection approaches are determined. Besides, this study can provide a new and objective method to interpret the FRA results and give us a better understanding how much the parameter variations can influence the FRA measurement results.Keywords
This publication has 11 references indexed in Scilit:
- Detection of transformer mechanical deformations by comparing different FRA connectionsInternational Journal of Electrical Power & Energy Systems, 2017
- Inter disc fault location in transformer windings using SFRAIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Improved power transformer winding fault detection using FRA diagnostics – part 1: axial displacement simulationIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Characterization of transformer FRA signature under various winding faults2012
- Sensitivity and tolerance analysis for oscillator circuits simulated by Van der Pol models2012
- Mathematical Comparison Methods to Assess Transfer Functions of Transformers to Detect Different Types of Mechanical FaultsIEEE Transactions on Power Delivery, 2010
- High-Frequency Modeling of Power Transformers for Use in Frequency Response Analysis (FRA)IEEE Transactions on Power Delivery, 2008
- Diagnosing transformer faults using frequency response analysisIEEE Electrical Insulation Magazine, 2003
- Sensitivity analysis of periodically switched linear circuits using an adjoint network technique2003
- The Generalized Adjoint Network and Network SensitivitiesIEEE Transactions on Circuit Theory, 1969