Load-Damping Characteristic Control Method in an Isolated Power System With Industrial Voltage-Sensitive Load

Authors:

Abstract
Load-damping characteristic models the load response to the frequency deviation, which has important impact on system frequency response. The load-damping coefficient is normally considered as a constant, obtained from operational experiences in large-scale power systems or from detailed load models in isolated power systems. An industrial isolated power system for aluminum production driven by coal-fired power and large scale wind power is studied in this paper. Since the electrolytic aluminum load is driven by direct current, it is one type of voltage-sensitive load and does not respond to the frequency deviation. This paper proposes a load-damping characteristic control method for such isolated industrial power system with voltage-sensitive load. To decrease the maximum frequency deviation during transient process, a time-varying load-damping coefficient control scheme is presented. Simulation is done on real-time digital simulator (RTDS) and the results verify the effectiveness of the proposed control method.
Funding Information
  • Ministry of Science and Technology of China (Grant 2012AA050218)
  • National Natural Science Foundation of China (Grant 51477122)

This publication has 20 references indexed in Scilit: