Improved DGA method based on rules extracted from high-dimension input space
Authors:
- 16 August 2012
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in Electronics Letters
- Vol. 48 (17) , 1048-1049
Abstract
The diagnosis of incipient faults in power system elements such as transformers is usually based on the concentrations of dissolved gases existent in the insulation oil. There are consolidated DGA-based (dissolved gas analysis) methods in the literature, such as the Duval triangle. However, they present some limitations such as the existence of non-decision areas and erroneous results. Proposed is a simple methodology to improve the analysis of incipient faults based on rules extracted from a high-dimension space (21 attributes), formed by the gases concentrations and some of their interrelations. From such input space, the C4.5 method (decision tree) is used to extract a set of interpretable rules. Databases known in the DGA technical literature such as IEC TC 10 are adopted to analyse the proposed approach. When compared with a standard method, considering all data test folders in the performed 10-folder cross-validation statistical analysis, the extracted rules show greater accuracy with an error in the diagnosis of incipient faults of 6.25%, against 18.75% for the Triangle method in the worst case.Keywords
This publication has 10 references indexed in Scilit:
- Application of an artificial neural network in the use of physicochemical properties as a low cost proxy of power transformers DGA dataIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- DGA Interpretation Scheme Derived From Case StudyIEEE Transactions on Power Delivery, 2010
- An Integrated Neural Fuzzy Approach for Fault Diagnosis of TransformersIEEE Transactions on Power Delivery, 2008
- Top-Down Induction of Decision Trees Classifiers—A SurveyIEEE Transactions on Systems, Man and Cybernetics, Part C (Applications and Reviews), 2005
- Improving the IEC Table for Transformer Failure Diagnosis With Knowledge Extraction From Neural NetworksIEEE Transactions on Power Delivery, 2005
- Dissolved gas analysis using evidential reasoningIEE Proceedings - Science, Measurement and Technology, 2005
- Extension neural network for power transformer incipient fault diagnosisIEE Proceedings - Generation, Transmission and Distribution, 2003
- A review of faults detectable by gas-in-oil analysis in transformersIEEE Electrical Insulation Magazine, 2002
- Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databasesIEEE Electrical Insulation Magazine, 2001
- Induction of decision treesMachine Learning, 1986