Development and application of a PID auto-tuning method to a wastewater treatment process
Authors:
- 1 January 2008
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 2, 229-234
Abstract
This paper presents an application regarding a developed extension of the widely used relay-feedback PID auto-tuner. The proposed method consists of two steps: process identification and controller design. First, a non-iterative procedure is suggested for identification of one point on the process Nyquist curve. A second-order model (SOS) is obtained and then used for PID controller design based on the internal model principle (IMC). For the identification of the point on the Nyquist curve a relay in the feedback loop (as used in standard auto-tuning) which operates on the integral of the error is used. The method is illustrated on an application to a wastewater treatment process. In the considered process, the wastewater is treated in order to obtain an effluent having the substrate concentration within the standard limits. The performances of control algorithms are illustrated by simulation results. The influence of changing a design parameter in the desired closed loop behavior is shown.Keywords
This publication has 5 references indexed in Scilit:
- Predictive Control of aWastewater Treatment ProcessInternational Journal of Computers Communications & Control, 2007
- Handbook of PI and PID Controller Tuning Rules2003
- Predictive PID controllersIEE Proceedings - Control Theory and Applications, 2001
- The future of PID controlControl Engineering Practice, 2001
- Autotuning of PID Controllers1999