Local Condensation Heat Transfer Characteristics of Refrigerant R1234ze(E) Flow Inside a Plate Heat Exchanger
Authors:
- 23 March 2017
- journal article
- research article
- Published by Springer Nature in International Journal of Air-Conditioning and Refrigeration
- Vol. 25 (01)
Abstract
In the present study, local condensation heat transfer coefficients of the R1234ze(E) inside a vertical plate heat exchanger (PHE) were investigated experimentally. In the experiment, three vertical flow channels are formed in the test section where refrigerant flows downward in the middle channel and cooling water flows upward in other two channels. The test section consists of eight plates: two of them form a channel of chevron type PHE for refrigerant flow channel, other two flat plates are set for heat transfer measurements, and another consist on cooling water flow channel. Down flow of the condensing refrigerant R1234ze(E) in the center channel releases heat to other channels of cooling water. In order to measure local heat transfer characteristics, a total of 60 thermocouples were set at middle of flow direction and also in the right and left sides of plates in test section. Experiments were conducted for mass fluxes ranging from 10[ ]kg/m2s to 50[ ]kg/m2s. The measurement results show that local heat transfer coefficients decrease with increase of wetness with different values in horizontal direction. Further, characteristics of local heat flux and wall temperature distribution as a function of distance from inlet to outlet of refrigerant channel were explored in detail.Keywords
This publication has 15 references indexed in Scilit:
- A review of refrigerant R1234ze(E) recent investigationsApplied Thermal Engineering, 2016
- Evaporation heat transfer and pressure drop of ammonia in a mixed configuration chevron plate heat exchangerInternational Journal of Refrigeration, 2014
- Flow pattern map, heat transfer and pressure drops during evaporation of R-1234ze(E) and R134a in a horizontal, circular smooth tube: Experiments and assessment of predictive methodsInternational Journal of Refrigeration, 2013
- Experimental investigation of evaporation heat transfer and pressure drop of ammonia in a 60° chevron plate heat exchangerInternational Journal of Refrigeration, 2012
- Thermodynamic properties of eight fluorinated olefinsInternational Journal of Refrigeration, 2010
- Heat transfer and pressure drop during HFC refrigerant vaporisation inside a brazed plate heat exchangerInternational Journal of Heat and Mass Transfer, 2007
- HFC-410A vaporisation inside a commercial brazed plate heat exchangerExperimental Thermal and Fluid Science, 2007
- Saturated flow boiling heat transfer and pressure drop of refrigerant R-410A in a vertical plate heat exchangerInternational Journal of Heat and Mass Transfer, 2002
- Condensation heat transfer and pressure drop of refrigerant R-134a in a plate heat exchangerInternational Journal of Heat and Mass Transfer, 1999
- Evaporation Heat Transfer and Pressure Drop of Refrigerant R-134a in a Plate Heat ExchangerJournal of Heat Transfer, 1999