Abstract
Despite growing renewable energy integration, curtailments persist, causing reverse power flows, congestion and operational issues, such as instability and frequency deviations. Battery energy storage can mitigate these impacts by rapidly absorbing and supplying power. This study targets isolated, high‑PV grids where HV/MV utility substations experience midday exports (reverse power flows) and proposes to nearly zero each substation’s daily net demand, by optimally charging/discharging distributed Battery Energy Storage Systems (BESS). We develop a hybrid heuristic–convex framework coupling Linear Programming dispatch with a Genetic Algorithm for parameter tuning and an AI (Deep Neural Networks) component to support decisions under variable net‑load conditions. The approach is validated on the Cyprus power system using 30‑min net‑load real data from transmission/distribution substations. Results show that substations equipped with BESS can markedly reduce energy imported from the transmission grid and excess PV energy exported back to the network during midday, by about ~60% and up to ~90%, respectively. The analysis also indicates that the increased local self‑consumption within the substations leads to the reduction in both minimum and peak conventional generation requirements. This is achieved by lowering average ramp rates by ~16% and contributing to a smoother system residual‑load profile (“duck curve”). These outcomes are particularly valuable for isolated systems like Cyprus that rely on imported fossil fuels and fluctuating domestic renewables.