Study on transient recovery voltage distribution mechanism and grading capacitor of double-break vacuum circuit breaker
Authors:
- 1 September 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 10932941,p. 501-504
Abstract
To keep the uniform distribution of the transient recovery voltage (TRV) across each vacuum interrupter (VI) is very important for the breaking capability of double-break vacuum circuit breakers (VCBs). According to the transient equivalent circuit of double-break VCBs, a mathematical model describing the TRV distribution characteristics was established; it revealed that the bias of TRV distribution was caused by the stray capacitance and the imbalanced post-arc plasma characteristics in each VI. The validity of the TRV distribution model was proved by simulation results based on a vacuum arc model. The experimental results under different values of grading capacitors demonstrated their effectiveness in improving the even degree of the TRV distribution in double-break VCBs. However, too large grading capacitor significantly magnified the amplitude and duration of the reignition current, which was detrimental to the successful breaking of double-break VCBs. It is advisable for this reason to limit the value of grading capacitors to those ranges which can guarantee sufficiently improve the TRV distribution.Keywords
This publication has 5 references indexed in Scilit:
- Relationship Between the Voltage Distribution Ratio and the Post Arc Current in Double-Break Vacuum Circuit BreakersIEEE Transactions on Plasma Science, 2009
- Interruption characteristics of double-break vacuum circuit breakersIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Withstand Voltage Characteristics of Two Series Vacuum InterruptersIEEE Transactions on Plasma Science, 2007
- Influence of grading capacitors on the breaking performance of a 24-kV vacuum breaker series designIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- Influence of grading capacitors on the breaking capacity of two vacuum interrupters in seriesIEEE Transactions on Dielectrics and Electrical Insulation, 1999