Optimizing solution of fault location

Authors:
  • CZChen Zheng
    Chen Zheng
  • HXHe Xuanzhou
    He Xuanzhou
  • WKWang Kehong
    Wang Kehong
  • LCLuo Chengmu
    Luo Chengmu

Abstract
This paper describes an assembled transmission line fault location algorithm based on one-terminal electrical quantities. It uses a fault location algorithm based on measurement impedance to calculate a fault section of a transmission line, then it uses a wavelet transform fault location algorithm based on current traveling wave to pinpoint the fault position. This algorithm deals with the conflict between accuracy and robustness of fault location algorithm successfully. The computer simulation demonstrates that the assembled fault location algorithm holds high robustness and high accuracy.

This publication has 1 reference indexed in Scilit: