Time history analysis for investigation of dynamic behavioral characteristics of uninterruptible power supply system
- 13 March 2022
- journal article
- research article
- Published by Taylor & Francis in Journal of Structural Integrity and Maintenance
- Vol. 7 (2) , 91-109
Abstract
This paper presents a seismic investigation of an uninterruptible power supply system (UPS) through triaxial shake table tests. A 100-kVA uninterruptible power supply system compliant with IEC-60950 was selected as the test specimen. The input acceleration time histories were generated based on the ICC-ES AC156 code, with scaling factors ranging from 25% to 600%. Based on the test results, the damage of the UPS and dynamic characteristics of this device were evaluated and explained in terms of fundamental frequency, damping ratio, acceleration time history response, dynamic amplification factor, and relative displacement. In addition, a simplified analytical model was proposed, and a parametric study was conducted to understand the dynamic characteristics of the UPS.Keywords
This publication has 7 references indexed in Scilit:
- Study on Seismic Performance of a Mold Transformer through Shaking Table TestsApplied Sciences, 2020
- Seismic Vulnerability Assessment of Hybrid Mold Transformer Based on Dynamic AnalysesApplied Sciences, 2019
- Evaluation of seismic dynamic behaviour of drywall partitions, façades and ceilings through shake table testingEngineering Structures, 2019
- Experimental assessment of the seismic performance of hospital cabinets using shake table testingEarthquake Engineering & Structural Dynamics, 2018
- Shake table tests for the seismic assessment of hollow brick internal partitionsEngineering Structures, 2014
- Accuracy of the half-power bandwidth method with a third-order correction for estimating damping in multi-DOF systemsEarthquake Engineering and Engineering Vibration, 2013
- Fragility of Mechanical, Electrical, and Plumbing EquipmentEarthquake Spectra, 2010