Estimation of Additional PV Converter Losses Operating Under PF ≠ 1 Based on Manufacturer's Data at PF = 1
Open Access
- 14 January 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. 34 (1) , 540-553
Abstract
The increasing penetration of Photovoltaic (PV) systems in distribution networks often causes overvoltage problems. One solution to address this issue is the provision of reactive power (RP) by the PV converters. This can cause increased power losses on the PV converters leading to additional operational costs. However, the manufacturers of commercially available PV converters provide data regarding the converter losses only under unity power factor (PF). The data are also limited regarding the technical details of the PV converters. This paper presents a methodology to estimate analytically the power losses for two-level PV converters under RP provision based on the efficiency curves at PF=1 for different PV voltages and the limited information given in the PV converter datasheet. The losses are separately estimated for the DC/DC converter and the DC/AC inverter because the losses on the former are not affected by the RP, while the losses on the latter are. The method is validated with field measurements of PV converter losses under RP provision and with detailed simulations.Keywords
Funding Information
- European Union Horizon 2020 (764090)
This publication has 24 references indexed in Scilit:
- Photovoltaic penetration issues and impacts in distribution network – A reviewRenewable and Sustainable Energy Reviews, 2016
- Thermal Performance and Reliability Analysis of Single-Phase PV Inverters With Reactive Power Injection Outside Feed-In Operating HoursIEEE Journal of Emerging and Selected Topics in Power Electronics, 2015
- Power losses analysis of two-levels and three-levels PWM inverters handling reactive power2015
- An accurate model for simulating energetic behavior of PV grid connected invertersSimulation Modelling Practice and Theory, 2014
- From distribution networks to smart distribution systems: Rethinking the regulation of European electricity DSOsUtilities Policy, 2014
- A Smart Strategy for Voltage Control Ancillary Service in Distribution NetworksIEEE Transactions on Power Systems, 2014
- Mathematical models for efficiency of inverters used in grid connected photovoltaic systemsRenewable and Sustainable Energy Reviews, 2014
- Combined Central and Local Active and Reactive Power Control of PV InvertersIEEE Transactions on Sustainable Energy, 2014
- Methodology for the optimal design of transformerless grid-connected PV invertersIET Power Electronics, 2012
- A new simple analytical method for calculating the optimum inverter size in grid-connected PV plantsElectric Power Systems Research, 2010