Abstract
Different transformer connections have different influences on the imbalance current introduced by the electric traction load. From transformers' symmetrical components matrices, the conditions under which there will be lest current injected into the primary windings of the transformer are studied. Capacitors or inductors can be installed to compensate the traction load to reach these conditions. Based on the deduced balance criteria, the compensation capacities for several specially connected transformers are researched. Analysis found out that for Scott transformer, Le-Blanc transformer and Modified Wood-bridge transformer, it is useful to install combination of inductors and capacitors on the secondary winding of transformers in order to reduce imbalance current.Keywords
This publication has 3 references indexed in Scilit:
- A novel approach to power factor control and balancing problems2002
- Three phase models of specially connected transformersIEEE Transactions on Power Delivery, 1996
- Network modelling of traction substation transformers for studying unbalance effectsIEE Proceedings - Generation, Transmission and Distribution, 1995