Control strategy for three-phase converter under unbalanced grid voltage conditions considering line loss
- 1 September 2014
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 5790-5796
Abstract
This paper proposes a novel control scheme for minimizing the line loss of three-phase converters under unbalanced grid voltages. Most prior works focus on balancing phase currents or eliminating dc-link voltage ripples. However, they do not consider rms currents, so the efficiency may be lowered. In this paper, the optimal current reference is proposed to minimize sum of squares of rms currents in three lines. As a result of the proposed strategy, the efficiency of both converter itself and overall power system can be enhanced. Also, we calculate another optimal solution for removing active power ripples and verify that it coincides with previous works. Nevertheless, the corresponding control algorithm utilizes only line-to-line voltages, not positive- and negative-sequence ones; therefore, the proposed scheme does not include an extraction of sequential components and exhibits simpler implementation than its conventional counterpart. Experimental results prove the validity and the effectiveness of the proposed method.Keywords
This publication has 17 references indexed in Scilit:
- DC Offset Error Compensation for Synchronous Reference Frame PLL in Single-Phase Grid-Connected ConvertersIEEE Transactions on Power Electronics, 2012
- Enhanced Decoupled Double Synchronous Reference Frame Current Controller for Unbalanced Grid-Voltage ConditionsIEEE Transactions on Power Electronics, 2012
- A Stationary Reference Frame Grid Synchronization System for Three-Phase Grid-Connected Power Converters Under Adverse Grid ConditionsIEEE Transactions on Power Electronics, 2012
- High-Performance Digital Resonant Controllers Implemented With Two IntegratorsIEEE Transactions on Power Electronics, 2010
- Multiresonant Frequency-Locked Loop for Grid Synchronization of Power Converters Under Distorted Grid ConditionsIEEE Transactions on Industrial Electronics, 2010
- Accurate and Less-Disturbing Active Antiislanding Method Based on PLL for Grid-Connected ConvertersIEEE Transactions on Power Electronics, 2010
- Decoupled Double Synchronous Reference Frame PLL for Power Converters ControlIEEE Transactions on Power Electronics, 2007
- Stationary frame current regulation of PWM inverters with zero steady-state errorIEEE Transactions on Power Electronics, 2003
- New control scheme of three-phase PWM AC/DC converter without phase angle detection under the unbalanced input voltage conditionsIEEE Transactions on Power Electronics, 2002
- A novel control method for input output harmonic elimination of the PWM boost type rectifier under unbalanced operating conditionsIEEE Transactions on Power Electronics, 2001