Parallel Interruption of Heavy Direct Current by Vacuum Circuit Breakers
Authors:
- 1 May 1980
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-99 (3) , 1119-1129
Abstract
A newly developed d.c. circuit breaker successfully interrupts the current up to 130 kA d.c. under 44 kV d.c. recovery voltage. The breaker also can carry out the respective 4000 times operations of the above breaking duty every ten minutes without any trouble. The essential breaking mechanism is composed of two series and four parallel construction of vacuum valves with current commutation capacitor.Keywords
This publication has 4 references indexed in Scilit:
- Vacuum arc under an axial magnetic field and its interrupting abilityProceedings of the Institution of Electrical Engineers, 1979
- High Current Vacuum Arcs Stabilized by Axial Magnetic FieldsIEEE Transactions on Power Apparatus and Systems, 1973
- Interruption ability of vacuum interrupters subjected to axial magnetic fieldsProceedings of the Institution of Electrical Engineers, 1972
- Switching in High Vacuum EnviromentIEEE Transactions on Component Parts, 1963