Surface-Integrated Electric Field Sensor for the Detection of High-Voltage Power Lines
Open Access
Abstract
When a drone is used for inspection of facilities, there are often cases in which high-voltage power lines interfere, resulting in the drone being caught or falling. To prevent this type of incident, drones must be capable of detecting high-voltage power lines. Typically, a strong electric field is formed around the high-voltage lines. To detect the electric fields around high-voltage lines, this study proposes an electric field sensor that may be integrated within the body of a drone. In a laboratory environment, a voltage of 25 kV was applied to an overhead line, and the induced voltage in the proposed sensor was measured at various electric field intensities. Over an electric field range of 0.5 to 10.1 kV/m, a voltage of 0 to 0.77 V was measured with each proposed sensor. In addition, the electric field and the voltage induced in the sensor were measured in a real-world railway environment with overhead lines. Under these conditions, the proposed sensor has the compensated value of 4.5 when the measured electric field was 4.05 kV/m. Therefore, the proposed sensor may be applied in drones to measure large electric fields and to detect the presence of high-voltage lines in its vicinity.Keywords
Funding Information
- Korea Railroad Research Institute (This work was supported by a grant from the R&D Program of the Korea Railroad Re-search Institute)
This publication has 11 references indexed in Scilit:
- Simulation and Test of a Contactless Voltage Measurement Method for Overhead Lines Based on Reconstruction of Integral Node ParametersSensors, 2019
- Method and Experimental Study of Voltage Measurement Based on Electric Field Integral With Gauss–Legendre AlgorithmIEEE Transactions on Instrumentation and Measurement, 2019
- Electrically Small Dipole Antenna Probe for Quasistatic Electric Field Measurements in Transcranial Magnetic StimulationIEEE Transactions on Magnetics, 2018
- Model, Design, and Testing of Field Mill Sensors for Measuring Electric Fields Under High-Voltage Direct-Current Power LinesIEEE Transactions on Industrial Electronics, 2017
- Study and Experiment on Non-Contact Voltage Sensor Suitable for Three-Phase Transmission LineSensors, 2015
- Research and Experiments on a Unipolar Capacitive Voltage SensorSensors, 2015
- LSD: A Fast Line Segment Detector with a False Detection ControlIEEE Transactions on Pattern Analysis and Machine Intelligence, 2008
- Standard probes for electromagnetic field measurementsIEEE Transactions on Antennas and Propagation, 1993
- Limitations on the Size of Miniature Electric-Field ProbesIEEE Transactions on Microwave Theory and Techniques, 1984
- Electric field probes--A reviewIEEE Transactions on Antennas and Propagation, 1983