Numerical Investigation on the Detection of Vacuum Interrupter Pressure Based on Pirani Method

Authors:

Abstract
Vacuum has excellent electrical insulation properties, and high vacuum is a decisive factor in the normal operation of the vacuum circuit breakers (VCBs). When the pressure in vacuum interrupter is higher than $10^{-1} \mathrm{~Pa}$, the dielectric strength will be significantly reduced and seriously affect the current breaking. For vacuum interrupter, monitoring the vacuum state continuously is of great importance to the stability of the VCBs and the safe operation of the power system. In this paper, the vacuum state detection scheme based on the Pirani method is investigated. A small iron sheet is welded to the outside of the shield, which can be heated by applying a high-frequency magnetic field. The pressure inside the interrupter is determined by detecting the variation of the resistance of the iron piece when it cools down, which depends on the pressure in the interrupter. The influence of the thickness of the target piece and the size of the welding point was analyzed with COMSOL Multiphysics. According to the simulation results, the lowest pressure that can be distinguished by this method is expected to be lower than $10^{-2} \mathrm{~Pa}$.