Insulation structure design and electric field simulation of 500 kV isolation energy supply transformer for HVDC breaker
Authors:
Open Access
- 21 April 2021
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in High Voltage
- Vol. 7 (1) , 185-196
Abstract
The high‐voltage isolated energy supply transformer (HIET) is the key component of the HVDC breaker, which is used for energy transmission and the potential isolation. There is a lack of research results that can meet engineering applications at home and abroad. The design of a 500 kV HIET with dry‐type insulation is proposed, using 10 cascade connected 50 kV sub‐transformers (STs), which uses silicon rubber suitable for DC voltage as the main insulation material. High‐voltage (HV) winding of ST adopts double‐shielding structure of coil semi‐conductive shielding and inner semi‐conductive shielding to improve electric field distribution. The simulation analysis of an electric field at different insulation thicknesses and temperatures shows that the electric field decreases with an increase in thickness of insulation. When the thickness is greater than 25 mm, the electric field reduction effect is significantly weakened. The electric field is closely related to temperature, when at 20°C, the electric field between double‐shielding is relatively uniform. When at 70°C, the inner shielding electric field is much higher than coil shielding, and undergoes obvious reversal. In addition, the 500 kV HIET's electric field has been analysed. The 50 0kV HIET prototype has been manufactured and passed the type test, and successfully applied to the 500 kV Zhangbei DC grid project.Keywords
This publication has 18 references indexed in Scilit:
- A Static Field Equivalence Method for Simulation of Fitting Surface Electric Field of 500 kV DC Yards in Converter Stations2018
- Electric field evaluation and optimization of shielding electrodes for high voltage apparatus in ±1100 kV indoor DC yardIEEE Transactions on Dielectrics and Electrical Insulation, 2018
- Research and application on multi‐terminal and DC grids based on VSC‐HVDC technology in ChinaHigh Voltage, 2017
- Investigation on the electrical characterization of silicone rubber using DC conductivity measurement2016
- Space charge behavior of silicone rubber nanocomposites with thermal step methodJapanese Journal of Applied Physics, 2016
- Design of integrated supervisory control system for 110 kV dry-type transformer2015
- R&D and application of voltage sourced converter based high voltage direct current engineering technology in ChinaJournal of Modern Power Systems and Clean Energy, 2014
- Analysis of the electric field distribution on insulating supports of dry‐type transformers under high temperatureIET Electric Power Applications, 2013
- HVDC Circuit Breakers: A Review Identifying Future Research NeedsIEEE Transactions on Power Delivery, 2011
- Insulator surface charge accumulation under impulse voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2004