Effect of arcing on DC flashover performance of contaminated porcelain insulators for various suspension patterns at high altitudes
Authors:
- Hua WenHWHua Wen
- Ruihai LiRLRuihai Li
- Yi MaYMYi Ma
- 13 June 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 15 (3) , 783-791
Abstract
This paper presents an analysis of the arcing and flashover performance of contaminated dc insulators of various suspension patterns at high altitudes (1970 m). The experiments tested two types of dc insulators, a bell-type insulator and a tri-shed suspension insulator. The experimental results show that dc arcs play an important role in the flashover performance since they levitate more easily from the porcelain surfaces at high altitudes than at sea level. For heavily contaminated insulators, the relationship between the insulator length and the flashover voltage per insulator unit is affected by the arc development path, and is lower for shorter insulator strings (10 to 20 insulator units). With a non-uniform contamination distribution between the top and bottom insulator surfaces, the arcs propagate close to the insulator surface, resulting in a higher flashover voltage than with uniform contamination. The Y-string configuration appears to lead to much lower flashover voltages than in I- and V-string insulators. With the latter, the arc propagation path is greatly influenced by the angle between the two insulator strings with the flashover voltages for both bell-type and tri-shed insulators increasing with the angle but apparently due to different mechanisms. Experimental results indicate that the bell-type insulator has better flashover characteristic; than the tri-shed insulator.Keywords
This publication has 18 references indexed in Scilit:
- Arc propagation analysis on polluted insulators based on the leakage current measurement2003
- DC flashover characteristics of the contaminated insulators under low atmospheric pressure2003
- Effect of climatic conditions on contamination flashover voltage of insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 1997
- Dynamic arc modeling of pollution flashover of insulators under DC voltageIEEE Transactions on Electrical Insulation, 1993
- Calculation of DC and AC flashover voltage of polluted insulatorsIEEE Transactions on Electrical Insulation, 1990
- Progress in outdoor insulation research in ChinaIEEE Transactions on Electrical Insulation, 1990
- Insulator pollution performance at high altitude: major trendsIEEE Transactions on Power Delivery, 1989
- A study on the profile of HVDC insulators-mathematical modeling and design considerationsIEEE Transactions on Electrical Insulation, 1989
- Polarity effect in DC withstand voltages of contaminated surfacesIEEE Transactions on Electrical Insulation, 1988
- Performance of Contaminated Insulators Tested from 200 Kv to 1000 Kv DCIEEE Transactions on Electrical Insulation, 1981