Transient overvoltage suppression of LCC‐HVDC sending‐end system based on DC current control optimisation
Authors:
Open Access
- 9 May 2024
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Energy Systems Integration
- Vol. 6 (2) , 182-195
Abstract
The receiving‐end system AC fault of the line‐commutated‐converter‐based high voltage direct current (LCC‐HVDC) will lead to commutation failure of the inverter side. During the fault and its recovery, AC transient low voltage and transient overvoltage (TOV) will occur in the sending‐end system. The TOV has the risk of triggering the disorderly off‐grid of the nearby renewable power generations. Besides, in a serious situation, it will threaten the power system to maintain a secure and steady operation. Therefore, the authors analyse the mechanism involved in the AC transient voltage during the AC fault and the recovery period first. It reveals that the key factor causing the TOV of the sending‐end system is the setting of the DC current reference value. Then, a DC current reference value limit method based on the AC TOV sampling value is proposed, which is used to accelerate DC current recovery and suppress the TOV of the sending‐end system. Finally, the effectiveness of the designed control method has been confirmed through electromagnetic transient simulations using the CIGRE HVDC benchmark model and a ±800 kV HVDC transmission system model situated in Northwest China.Keywords
This publication has 10 references indexed in Scilit:
- Concept and Definition of Dynamic Symmetrical Components With Time-Varying Amplitude and FrequencyIEEE Transactions on Energy Conversion, 2022
- Truncation Number Selection of Harmonic State-Space Model Based on the Floquet Characteristic ExponentIEEE Transactions on Industrial Electronics, 2022
- Overvoltage Suppression Under Commutation Failure Based on Improved Voltage-Dependent Current Order Limiter Control StrategyIEEE Transactions on Industry Applications, 2022
- Analysis of Transient Voltage Disturbances in LCC-HVDC Sending Systems Caused by Commutation FailuresIEEE Transactions on Power Delivery, 2022
- Overvoltage Suppression Strategy for Sending AC Grid With High Penetration of Wind Power in the LCC-HVdc System Under Commutation FailureIEEE Transactions on Power Electronics, 2021
- Reactive Power Control Strategy for Inhibiting Transient Overvoltage Caused by Commutation FailureIEEE Transactions on Power Systems, 2021
- Quantifying the Contribution of Dynamic Reactive Power Compensators on System Strength at LCC-HVdc Converter TerminalsIEEE Transactions on Power Delivery, 2021
- Analytical Expression on Transient Overvoltage Peak Value of Converter Bus Caused by DC FaultsIEEE Transactions on Power Systems, 2021
- Small-Signal Modeling and Analysis of MMC Under Unbalanced Grid Conditions Based on Linear Time-Periodic (LTP) MethodIEEE Transactions on Power Delivery, 2020
- Nonlinear Photovoltaic Controller Design to Suppress Overvoltage at the Sending End of HVDC Transmission Systems2019