Thermodynamic Performance Assessment of a CO2 Supermarket Refrigeration System with Auxiliary Compression Economization by using Advanced Exergy Analysis
Open Access
- 29 November 2017
- journal article
- Published by International Centre for Applied Thermodynamics (ICAT) in International Journal of Thermodynamics
- Vol. 20 (4) , 220-227
Abstract
Supermarkets are currently one of the most vital service facilities, whose number of installations is ever-growing in both developed and developing countries. On the other hand, these applications feature a copious indirect contribution to the ongoing climate change, as well as a massive use of potent greenhouse gases. In an attempt to promote climate-friendlier technologies in commercial refrigeration sector, “CO 2 only” (transcritical CO 2 or pure CO 2 ) refrigeration systems have become the mainstream of new food retails worldwide. In particular, in the last few years parallel (or auxiliary) compression has taken root in food retails as a means to enhance the energy efficiency of pure CO 2 units. The thermodynamic performance of such a promising solution can be suitably assessed with the aid of the advanced exergy analysis. The results obtained at the design outdoor temperature of 40 °C showed that the main compressor has the highest priority of enhancement, whereas the high-pressure expansion valve needs to be replaced with a device for expansion work recovery. Also, close attention had to be paid to both the gas cooler and the auxiliary compressor. The former can be improved mainly by enhancing the other components, whereas the irreversibilities related to the latter can be decreased by improving both the compressor itself and the remaining components. Finally, the implemented sensitivity analysis revealed that the improvement in the efficiency of the main compressor should be seriously considered on the part of the manufacturers.Keywords
This publication has 22 references indexed in Scilit:
- Comparative Assessment of Low-GWP Based Refrigerating Plants Operating in Hot ClimatesEnergy Procedia, 2017
- Advanced exergy analysis of transcritical CO2 heat pump system based on experimental dataSādhanā, 2016
- Advanced exergy analyses of an ejector expansion transcritical CO2 refrigeration systemEnergy Conversion and Management, 2016
- Conventional and advanced exergy analysis of an ejector refrigeration systemApplied Energy, 2015
- Experimental analysis of R744 parallel compression cycleApplied Energy, 2014
- Advanced exergy analysis of a trigeneration system with a diesel–gas engine operating in a refrigerator plant buildingEnergy and Buildings, 2014
- Splitting the exergy destruction into avoidable and unavoidable parts of a gas engine heat pump (GEHP) for food drying processes based on experimental valuesEnergy Conversion and Management, 2013
- Numerical model for thermoeconomic diagnosis in commercial transcritical/subcritical booster refrigeration systemsEnergy Conversion and Management, 2012
- Conventional thermodynamic and advanced exergetic analysis of a refrigeration machine using a Voorhees’ compression processEnergy Conversion and Management, 2012
- Thermodynamic analysis of transcritical CO2 booster refrigeration systems in supermarketEnergy Conversion and Management, 2011