Extended impedance-based fault location formulation for unbalanced underground distribution systems
- 1 July 2008
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-8
Abstract
Underground distribution systems are commonly exposed to permanent faults. Due to specific construction characteristics, visual inspection for fault location cannot be performed. To overcome this limitation, accurate fault location techniques must be applied. In this paper, an extended impedance-based fault location formulation for unbalanced underground distribution systems is described considering single line-to-ground faults. The technique uses only local voltages and currents as input data. An iterative algorithm for cable capacitive current compensation in the fault location formulation is proposed. The formulation focuses an easily practical implementation and is based on typical available systempsilas data, as lines impedance and admittance matrices, and also system loads. Test simulations on a real data underground distribution system demonstrate the proposed extensions improvements. The algorithm performance presents negligible fault resistance, distance, and inception angle variation effects.Keywords
This publication has 15 references indexed in Scilit:
- Unbalanced Underground Distribution Systems Fault Detection and Section Estimation2007
- Impedance-Based Fault Location Experience2006
- Transmission Line Models for Steady-State and Transients Analysis2005
- A robust phase-coordinates frequency-dependent underground cable model (zCable) for the EMTPIEEE Transactions on Power Delivery, 2003
- Removal of decaying DC in current and voltage signals using a modified Fourier filter algorithmIEEE Transactions on Power Delivery, 2001
- A fault location technique for rural distribution feedersIEEE Transactions on Industry Applications, 1993
- Simulation of transients in underground cables with frequency-dependent modal transformation matricesIEEE Transactions on Power Delivery, 1988
- Accurate Modelling of Frequency-Dependent Transmission Lines in Electromagnetic Transient SimulationsIEEE Transactions on Power Apparatus and Systems, 1982
- Tensorial Analysis of Integrated Transmission Systems Part I. The Six Basic Reference FramesTransactions of the American Institute of Electrical Engineers, 1951
- Wave Propagation in Overhead Wires with Ground ReturnBell System Technical Journal, 1926