Optimal Tap Setting of Voltage Regulation Transformers in Unbalanced Distribution Systems
Authors:
- 11 February 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 31 (1) , 256-267
Abstract
In this paper, we propose a method to optimally set the tap position of voltage regulation transformers in distribution systems. We cast the problem as a rank-constrained semidefinite program (SDP), in which the transformer tap ratios are captured by 1) introducing a secondary-side “virtual” bus per transformer, and 2) constraining the values that these virtual bus voltages can take according to the limits on the tap positions. Then, by relaxing the non-convex rank-1 constraint in the rank-constrained SDP formulation, one obtains a convex SDP problem. The tap positions are determined as the ratio between the primary-side bus voltage and the secondary-side virtual bus voltage that result from the optimal solution of the relaxed SDP, and then rounded to the nearest discrete tap values. To efficiently solve the relaxed SDP, we propose a distributed algorithm based on the alternating direction method of multipliers (ADMM). We present several case studies with single- and three-phase distribution systems to demonstrate the effectiveness of the distributed ADMM-based algorithm, and compare its results with centralized solution methods.Keywords
This publication has 18 references indexed in Scilit:
- An Optimal and Distributed Method for Voltage Regulation in Power Distribution SystemsIEEE Transactions on Power Systems, 2014
- Optimal Dispatch of Photovoltaic Inverters in Residential Distribution SystemsIEEE Transactions on Sustainable Energy, 2014
- Optimal tap settings for voltage regulation transformers in distribution networks2013
- Distributed Optimal Power Flow for Smart MicrogridsIEEE Transactions on Smart Grid, 2013
- Zero Duality Gap in Optimal Power Flow ProblemIEEE Transactions on Power Systems, 2011
- Distributed Optimization and Statistical Learning via the Alternating Direction Method of MultipliersFoundations and Trends in Machine Learning, 2011
- Zero duality gap for classical opf problem convexifies fundamental nonlinear power problems2011
- Optimal transformer tap selection using modified barrier-augmented lagrangian methodIEEE Transactions on Power Systems, 2003
- Advanced transformer control modeling in an optimal power flow using Newton's methodIEEE Transactions on Power Systems, 2000
- Discrete shunt controls in a Newton optimal power flowIEEE Transactions on Power Systems, 1992