Legionnaires' Disease Associated With a Hospital Water System

Authors:
  • CHCharles M. Helms
    Charles M. Helms
  • RMR. Michael Massanari
    R. Michael Massanari
  • RWRichard P. Wenzel
    Richard P. Wenzel
  • MPMichael A. Pfaller
    Michael A. Pfaller
  • NMNelson P. Moyer
    Nelson P. Moyer
  • NHNancy Hall
    Nancy Hall
  • SSStephen Streed
    Stephen Streed
  • WJWilliam Johnson
    William Johnson
  • WHWilliam J. Hausler
    William J. Hausler
  • LWLaverne A. Wmtermeyer
    Laverne A. Wmtermeyer

Abstract
In 1981, sixteen cases of nosocomial legionellosis occurred among 456 patients admitted to a new hematology-oncology unit (35 per 1000 admissions). Monoclonal antibody typing and restriction endonuclease plasmid analysis identified a unique strain (09,04) ofLegionella pneumophilaserogroup 1 isolated from both patients and water outlets. Continuous hyperchlorination of the hot and cold water began in January 1982, and chlorine levels of 3 to 5 mg/L have been maintained most recently. Water samples have been consistently negative forLegionellafor more than five years. Four sporadic cases of nosocomial legionellosis have occurred in the hematology-oncology unit during the same period (one per 1000 admissions) associated with a different strain ofL pneumophilaserogroup 1 (09,00). The environmental reservoir(s) ofL pneumophilaserogroup 1 in these cases has not been identified. Levels of trihalomethanes (potential carcinogens) were high (>100 μg/L) when chlorine levels of hot water exceeded 4 mg/L. Some corrosion damage to the water distribution system has occurred: the average number of leaks per month increased steadily from zero in 1982 to 5.2 in 1986. The chlorinator installation costs were $75 800, and annual operation expenses were $12 500. Continuous hyperchlorination is a promising but still experimental technique for control of nosocomial legionellosis. In our experience, epidemic disease has been controlled, but sporadic cases have continued to occur. (JAMA1988;259:2423-2427)