Abstract
This study proposes a fast static-security screening framework for contingency assessment in renewable-integrated power systems. The IEEE 118-bus system is modified by adding a 50 MW photovoltaic unit and an 80 MW wind generator. The framework combines DC load-flow-based N-1/N-2 screening, AC power-flow validation, fast Fourier transform (FFT) spatial spectral feature extraction, and support vector machine (SVM) classification. The DC model is used as a preliminary screening engine rather than a full substitute for AC power flow, and its limitations are evaluated through case-by-case AC/DC validation, line-resistance sensitivity, and reactive-load sensitivity. Results identify lines 65-68, 38-65, and 8-5 as the most critical N-1 contingencies, while the combined outage of 65-68 and 23-24 gives the most severe N-2 case. FFT energy shows strong rank consistency with angle-deviation severity and complements LOI and L-index indicators. The SVM achieves 83.18% accuracy on a grouped holdout of unseen contingencies and 83.06% under grouped K-fold cross-validation. Stochastic renewable and ramp-event analyses show corridor-dependent severity changes. Scalability tests demonstrate practical screening capability while indicating the need for filtering and parallelization in very large systems.