Numerical Modeling of Perforated Tile Flow Distribution in a Raised-Floor Data Center
- 20 May 2010
- journal article
- Published by ASME International in Journal of Electronic Packaging
- Vol. 132 (2) , 021002
Abstract
This paper is centered on quantifying the effect of computer room and computer room air conditioning (CRAC) unit modeling on the perforated tile flow distribution in a representative raised-floor data center. Also, this study quantifies the effect of plenum pipes and perforated tile porosity on the operating points of the CRAC blowers, total CRAC air flow rate, and its distribution. It is concluded that modeling the computer room, the CRAC units, and/or the plenum pipes could make an average change of up to 17% in the tile flow rates with a maximum of up to 135% for the facility with 56% open tiles while the average and maximum changes for the facility with 25% open tiles are 6% and 60%, respectively.Keywords
This publication has 5 references indexed in Scilit:
- Modeling of data center airflow and heat transfer: State of the art and future trendsDistributed and Parallel Databases, 2007
- Distributed Leakage Flow in Raised-Floor Data Centers2005
- Airflow Uniformity Through Perforated Tiles in a Raised-Floor Data Center2005
- Raised-floor data center: perforated tile flow rates for various tile layouts2004
- Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data CentersHVAC&R Research, 2003