Harmonic distortion-based island detection technique for inverter-based distributed generation
Authors:
- 7 December 2009
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 3 (4) , 493-507
Abstract
A harmonic distortion-based island detection technique for inverter-based distributed generation (IBDG) is proposed. The proposed technique is classified as an active island detection technique and it is based on the voltage change at the point of common coupling (PCC) that occurs in islanding. To avoid island detection failure in case of a close matching between IBDG-generated power and load power, an active power–voltage locus is introduced to shift the reference active power for PCC voltage change, therefore breaking the IBDG-load power balance and transferring the operating point outside the non-detection zone. A new harmonic performance index, named harmonic amplification factor, is introduced to detect the island. This factor amplifies each harmonic component by its order. Besides the ability of detecting short circuit, the proposed technique can discriminate between islanding and other disturbances, as load change, grid voltage distortion and unbalance, and capacitor bank switching. The proposed technique is validated by Matlab/Simulink simulation and practically as well.Keywords
This publication has 41 references indexed in Scilit:
- A Power Line Signaling Based Technique for Anti-Islanding Protection of Distributed Generators—Part I: Scheme and AnalysisIEEE Transactions on Power Delivery, 2007
- Intelligent-Based Approach to Islanding Detection in Distributed GenerationIEEE Transactions on Power Delivery, 2007
- Impact of DG Interface Control on Islanding Detection and Nondetection ZonesIEEE Transactions on Power Delivery, 2006
- Current Injection for Active Islanding Detection of Electronically-Interfaced Distributed ResourcesIEEE Transactions on Power Delivery, 2006
- Performance Assessment of Active Frequency Drifting Islanding Detection MethodsIEEE Transactions on Energy Conversion, 2006
- Evaluation of Anti-Islanding Schemes Based on Nondetection Zone ConceptIEEE Transactions on Power Electronics, 2004
- An Islanding Detection Method for Distributed Generations Using Voltage Unbalance and Total Harmonic Distortion of CurrentIEEE Transactions on Power Delivery, 2004
- A detection algorithm for islanding-prevention of dispersed consumer-owned storage and generating unitsIEEE Transactions on Energy Conversion, 2001
- Determining the relative effectiveness of islanding detection methods using phase criteria and nondetection zonesIEEE Transactions on Energy Conversion, 2000
- A new approach to islanding detection of dispersed generators with self-commutated static power convertersIEEE Transactions on Power Delivery, 2000