Switching Capacitor Bank Back-to-Back to Underground Cables
Author:
- 4 February 2013
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 28 (2) , 1128-1137
Abstract
This paper addresses the capacitor bank switching back to back to underground cables. The high currents recorded during the capacitor bank switching occur due to the traveling waves in the underground cables. The detailed analytical study of the capacitive inrush currents is done. The closed-form expressions of the inrush current waveforms due to the initial current surges as well as due to the superposition of the initial and reflected current waves are derived. The formulas for the peak inrush current and its maximum rate of rise are obtained. The case study of the 24-kV capacitor bank switching back to back to the underground cables is described. The results of the field measurements are compared with the results of Electromagnetic Transients Program simulation. The dependence of the inrush current peak on the number of the cables, and the equivalent inductance between the capacitor bank and the substation busbar as well as on the cable length are analyzed. The inrush currents caused failures of the capacitor bank circuit breakers. Since the described capacitor inrush current significantly exceeds the “inrush current of the isolated capacitor bank,” the selection of the capacitor bank switchgear should be taken into account.Keywords
This publication has 4 references indexed in Scilit:
- Back-to-back energization of a 60kV cable network - inrush currents phenomenon2010
- Analytical Study of Voltage Magnification Transients Due to Capacitor SwitchingIEEE Transactions on Power Delivery, 2009
- The application of distribution system current transformers for high frequency transient based protection2004
- A General Formulation of Impedance and Admittance of CablesIEEE Transactions on Power Apparatus and Systems, 1980