Abstract
This paper presents an automatic method for locating faults based on the statuses of fault indicators that are telemetered to the distribution control center. The method constructs an undirected subgraph of the the part of the network that is relevant to the fault event; the vertices of this graph are areas that comprise the possibly faulted electrical equipment, and its edges are the fault indicators. Two graph marking approaches for fault location are discussed: a conventional marking approach that is adopted by the industry and an improved version of it, the downstream marking approach. This paper demonstrates that the downstream marking approach is superior to the conventional one, particularly in terms of immunity to fault indicators that fail to be set. Numerical results and comparisons are presented for unsymmetrical faults and on several networks.Keywords
This publication has 24 references indexed in Scilit:
- A Systematic Approach for Ranking Distribution Systems Fault Location Algorithms and Eliminating False EstimatesIEEE Transactions on Power Delivery, 2012
- Optimal placement of faulted circuit indicators in power distribution systemsElectric Power Systems Research, 2011
- Extended Fault-Location Formulation for Power Distribution SystemsIEEE Transactions on Power Delivery, 2009
- Automated Fault Location System for Primary Distribution NetworksIEEE Transactions on Power Delivery, 2005
- A New Fault Location Algorithm Using Direct Circuit Analysis for Distribution SystemsIEEE Transactions on Power Delivery, 2004
- Automated fault location and diagnosis on electric power distribution feedersIEEE Transactions on Power Delivery, 1997
- Optimal operation of distribution networksIEEE Transactions on Power Systems, 1996
- Planning of distribution feeder reconfiguration with protective device coordinationIEEE Transactions on Power Delivery, 1993
- A fault location technique for rural distribution feedersIEEE Transactions on Industry Applications, 1993
- New approach to directional fault location for overhead power distribution feedersIEE Proceedings C Generation, Transmission and Distribution, 1991