Development of adaptive distance relay for STATCOM connected transmission line
Authors:
- 1 December 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 248-253
Abstract
Flexible AC Transmission System (FACTS) devices are inserted into power grids in series, in shunt, and in some cases, both in shunt and series for the improved power transmission capability. They also improve the controllability, stability and power quality of the power system. Static Synchronous Compensator (STATCOM) is a shunt type FACTS device connected at the midpoint of the transmission line to maintain the voltage at desired level by injecting/absorbing the reactive power. These devices have fast dynamic response time, which overlap with the response time of the line protection distance relays. This interaction affects the performance of distance protection relay during line faults. In this paper the design and development of a new adaptive distance relaying scheme to mitigate the adverse effects of the STATCOM is presented. A ±100MVA 48 pulse STATCOM with associated control system, connected at the midpoint of a typical 400KV transmission system is selected for simulation. The line faults of different types at various locations of the line are simulated using EMTDC/PSCAD ® and the performance of newly developed adaptive distance protection scheme has been evaluated and efficacy of the proposed scheme is illustrated.Keywords
This publication has 9 references indexed in Scilit:
- Analysis of impedance relaying procedure effected by STATCOM operation2009
- Performance Comparison of Distance Protection Schemes for Shunt-FACTS Compensated Transmission LinesIEEE Transactions on Power Delivery, 2007
- Impact of Shunt-FACTS on Distance Protection of Transmission Lines2006
- FACTS2004
- Operation of impedance protection relays with the STATCOMIEEE Transactions on Power Delivery, 2002
- Thyristor-Based FACTS Controllers for Electrical Transmission Systems2002
- Understanding FACTS1999
- Operation of ±100 MVAr TVA STATCONIEEE Transactions on Power Delivery, 1997
- Development of a ±100 MVAr static condenser for voltage control of transmission systemsIEEE Transactions on Power Delivery, 1995